- Specifications - |
|
|
|
Capacity |
20,000kcal/h(17kw) |
Temperature Control Range |
10 ~60℃ |
Accuracy |
± 0.2℃ |
Humidity Control Range |
30 ~ 90% RH
|
Accuracy |
±5% |
Air Flow Rate |
100 ~ 1000CMH |
Test Core Size |
Max 400(W) X 300(H) X 100(D) |
Stability |
±0.2℃ S.P at Typical test point, ±0.5℃ S.P at Worst case |
Heating &Cooling rate |
1.5℃/min , 0.7℃/min Without product load |
Core Tunnel Specification |
Air flow stability : ±1% S.P Inc Nozzle D.P sensor |
Sensor |
±0.25% S.P Inc High Accuracy Nozzle D.P sensor |
Air flow Control |
Blower RPM, Bypass damper, and PID |
|
|
|
Construction |
Material |
Rolled acrylic & Stainless & Aluminum |
Outside Dimension |
Eva. Room 2500(W) X 6000(D) X 2700(H) |
|
|
Control |
Control |
Possible both automatic and manual |
Control Interface |
Directreading / LabVIEW softWare with PC Interface |
|
|
|